Underground Direct Burial 0.6/1kv Copper Conductor XLPE/PE Insulation Swa Armoured Power Cable
Product model: XLPE insulated PVC sheathed copper core low voltage power cable
Number of product cores: 1-5 cores
Product specifications: 1.5mm²--500mm²
Product colour: red, yellow, blue, green, black; other colours can be customized
Rated voltage: 0.6/1KV
The length of the whole plate: 500m (national standard full meter)
Maximum conductor temperature during normal operation: 70°C for PVC insulation, 90°C for XLPE insulation.
Installation and laying temperature: The installation and laying temperature of the cable should be not lower than 0C.
Maximum temperature of the cable conductor during short circuit (maximum duration not exceeding 5 seconds): PVC insulation - 160°C for conductor cross-section ≤ 300 mm2, 140°C for conductor cross-section > 300 mm2; 250°C for XLPE insulation.
Scope of application: This product is suitable for use in lines with an AC rated voltage U0/U of 0.6/1kV for transmission and distribution lines.
Minimum bending radius allowed: Single-core cable: 20D without armour, 15D with armour Multi-core cable: 15D without armour, 12D with armour Where: D - actual outer diameter of the cable.
Type | Description | Applicable scope | |
Cu | Al | ||
YJV | YJLV | Cu or Al conductor XLPE insulated PVC sheathed power cable | For laying indoor and outdoor, unable to bearextemal mechanical force but the tractive forceduring laying. Laying single core cable inmagnetic duct is not permissible. |
YJY | YJLY | Cu or Al conductor XLPE insulated PE sheathed power cable | |
YJV22 | YJLV22 | Cu or Al conductor XLPE insulated steel tape armored PVC sheathed power cable | For laying underground, able to bear externalmechanical force, but unable to bear largepulling force. |
YJV23 | YJLV23 | Cu or Al conductor XLPE insulated steel tape armored PE sheathed power cable | |
YJV32 | YJLV32 | Cu or Al conductor XLPE insulated steel wire armored PVC sheathed power cable | For laying underground along route withdifferent level, able to bear external mechanicalforce and moderate pulling force. |
YJV33 | YJLV33 | Cu or Al conductor XLPE insulated steel wire armored PE sheathed power cable | |
YJV42 | YJLV42 | Cu or Al conductor XLPE insulated thick steel wire armored PVC sheathedpower cable | |
YJV43 | YJLV43 | Cu or Al conductor XLPE insulated thick steel wire armored PE sheathed powercable |
Type | Cross Section | Stranding | Approx Weight | Approx Overall Diameter | Gland Size | Single Cleat | Nom. Max. DC-resist conductor 20° C | Current rating laid direct |
(mm²) | (mm) | KG/KM | (mm) | (mm) | (Ohm/km) | (Amp) | ||
SWAPVC 4X1.5 | 4 x 1.5 | 7/0.53 | 351 | 12.88 | 20s | 0.5 | 12.1 | 32 |
SWAPVC 4X2.5 | 4 x 2.5 | 7/0.67 | 429 | 14.43 | 20s | 0.6 | 7.41 | 42 |
SWAPVC 4X4.0 | 4 x 4.0 | 7/0.85 | 538 | 16.87 | 20 | 0.6 | 4.61 | 55 |
SWAPVC 4X6.0 | 4 x 6.0 | 7/1.04 | 670 | 17.87 | 20 | 0.7 | 3.08 | 69 |
SWAPVC 4X10 | 4 x 10 | 7/1.35 | 998 | 20.1 | 25 | 0.8 | 1.83 | 92 |
SWAPVC 4X16 | 4 x 16 | 7/1.70 | 1,272 | 22.4 | 25 | 0.9 | 1.15 | 119 |
SWAPVC 4X25 | 4 x 25 | 7/2.14 | 1,940 | 27 | 32 | 1 | 0.727 | 152 |
SWAPVC 4X35 | 4 x 35 | 7/2.52 | 2,390 | 30.1 | 32 | 1.2 | 0.524 | 182 |
SWAPVC 4X50 | 4 x 50 | 19/1.78 | 2,925 | 31.5 | 32 | 1.4 | 0.387 | 217 |
SWAPVC 4X70 | 4 x 70 | 19/2.14 | 4,200 | 37.4 | 40 | 1.6 | 0.268 | 266 |
SWAPVC 4X95 | 4 x 95 | 19/2.52 | 5,355 | 40.9 | 50s | 1.8 | 0.193 | 319 |
SWAPVC 4X120 | 4 x 120 | 37/2.03 | 6,925 | 46.6 | 50 | 2 | 0.153 | 363 |
SWAPVC 4X150 | 4 x 150 | 37/2.25 | 8,200 | 50.2 | 50s | 2 | 0.124 | 406 |
SWAPVC 4X185 | 4 x 185 | 37/2.52 | 9,975 | 55.8 | 63s | TC9 | 0.0991 | 458 |
SWAPVC 4X240 | 4 x 240 | 61/2.52 | 12,700 | 62.5 | 63 | TC10 | 0.0754 | 529 |
SWAPVC 4X300 | 4 x 300 | 61/2.85 | 15,275 | 67.4 | 75s | TC11 | 0.0601 | 592 |
SWAPVC 4X400 | 4 x 400 | 61/3.20 | 19,875 | 77 | 75 | TC12 | 0.047 | 667 |
Rated voltage 0.6/1kV insulated power cable is suitable for use in power systems of 1kV and below, and can be used in transmission systems and distribution systems as a carrier for power transmission.
Flame-retardant power cables have the characteristics of ordinary plastic power cables, but also have the characteristics of not easily catching fire or catching fire and delaying combustion only within a certain range, especially suitable for fire alarm, firefighting facilities, emergency evacuation and other fire emergency system distribution.
Halogen-free, low-smoke, flame-retardant power cables have the characteristics of ordinary plastic force cables and ordinary flame-retardant cables, but also have the characteristics of no halogen acid gas release when the cable is on fire, less smoke, less corrosive gas generation and good flame-retardant performance, etc. They are especially suitable for fire alarm, firefighting facilities, emergency evacuation and other fire emergency system distribution.